Our Profile
Rudra International - Profile
Float cum Boost Battery Charger
Imported from India
Manufacturer: Electro Star
Contractor/Distributor:
Supplied To: Modi Khola Hydropower Station
Technical Specifications for Float cum Boost Battery Charger
|
||
1 |
Type |
SRC Controlled Fully Automatic |
2
|
Applicable Standard
|
IEC |
3
|
Output Voltage |
110V |
4
|
Input Voltage Rating |
415V 3 Phase AC, 50 Hz |
5 |
Efficiency at 100% Output |
80% |
6 |
Normal VDC |
110V |
7 |
Boost VDC |
110V DC To 135V DC |
8 |
Float VDC |
110V DC To 121V DC |
9 |
Current Rated |
75 Amp |
10 |
Mode of Operation |
Automatic / Manual |
11 |
Ripple Current |
1% rms with battery |
12 |
Display of Output Current, Load and Charging Current |
Digital |
13 |
LCD Display for Input Voltage |
Yes |
14 |
Cooling |
Natural Air |
15 |
Alarm Relays |
6 Nos. |
16 |
Output Blocking Diode |
100A, 1000PIV |